cords cable industries |
|
Properties for Flame Retardant Low
Smoke(FRLS), Flame retardant(FR), Fire Survival(FS) & Low Smoke Zero
Halogen(LSZH)
|
|
Flame Retardant Low
Smoke(FRLS) Properties for Sheathing compounds
|
|
Min. Oxygen index as per ASTMD-2863
|
29%
|
|
Min. Temperature index as per ASTMD-2863
|
250 Deg.C
|
|
Max. HCL emission as per IEC-754-I
|
20% by weight
|
|
Max. Smoke density rating as per ASTMD-2843
|
60%
|
|
Flammability test for completed cables
|
Cables shall meet the flammability test requirements as per IEC-332-I,
IEC-332-III Cat A, B or C, IEEE-383, SS-424 1475 Class F3, IS:10810- Part 53
or part 61 or Part 62 as per specific requirement of customer.
|
|
Flame Retardant(FR)
Properties for Sheathing compounds
|
|
Min. Oxygen index as per ASTMD-2863
|
30%
|
|
Min. Temperature index as per ASTMD-2863
|
250 Deg.C
|
|
Flammability test for completed cables
|
Cables shall meet the flammability test requirements as per IEC-332-I,
IEC-332-III Cat A, B or C, IEEE-383, SS-424 1475 Class F3, IS:10810- Part 53
or part 61 or Part 62 as per specific requirement of customer.
|
|
Special test for Fire
Survival(FS) cables
|
|
Flammability test for completed cables
|
Cables shall meet the flammability test requirements as per IEC-331
|
|
Properties of Low Smoke
Zero Halogen(LSZH) compounds
|
|
Min. Oxygen index as per ASTMD-2863
|
35%
|
|
Min. Temperature index as per ASTMD-2863
|
280 Deg.C
|
|
Max. HCL emission as per IEC-754-I
|
2% by weight / 0.5% by weight as required
|
|
Max. Smoke density rating as per ASTMD-2843
|
20%
|
|
Flammability test for completed cables
|
Cables shall meet the flammability test requirements as per IEC-332-I,
IEC-332-III Cat A, B or C, IEEE-383, SS-424 1475 Class F3, IS:10810- Part 53
or part 61 or Part 62 as per specific requirement of customer.
|
|
|
|
|