600/1000V XLPE INSULATED, PVC INNER SHEATHED,ALUMINIUM WIRE ARMOURED,PVC OUTER SHEATHED SINGLE CORE COPPER CABLES CONFIRMING TO IEC-60502-1 |
Type
|
No. of cores and cross sectional area
|
Thickness of XLPE insulation
|
Thickness of inner sheath
|
Single layer of round aluminium wire armour
|
Thickness of outer sheath
|
Overall diameter of cable
|
Net weight of cable
|
D.C. Resistance at 200C
|
A.C. Resistance at 900C
|
Current Rating
|
Short Circuit current rating for 1 sec
|
|
|
(nom.) |
(Approx.) |
(nom.) |
(nom.) |
(Approx.) |
(Approx.) |
(max.) |
(max.) |
Direct in ground |
In Duct |
In Air |
|
UNIT |
No. x mm2 |
mm |
mm |
mm |
mm |
mm |
Kg/km |
Ohm/km |
Ohm/km |
Amps |
Amps |
Amps |
KA(rms) |
2XWY |
1C X 1.5 |
0.7 |
1.0 |
0.9 |
1.8 |
11 |
160 |
12.1 |
15.43 |
28 |
26 |
22 |
0.21 |
1C X 2.5 |
0.7 |
1.0 |
0.9 |
1.8 |
11.5 |
175 |
7.41 |
9.45 |
38 |
35 |
30 |
0.36 |
1C X 4 |
0.7 |
1.0 |
0.9 |
1.8 |
12.0 |
205 |
4.61 |
5.88 |
49 |
46 |
39 |
0.57 |
1C X 6 |
0.7 |
1.0 |
0.9 |
1.8 |
12.5 |
230 |
3.08 |
3.93 |
62 |
59 |
49 |
0.86 |
1C X 10 |
0.7 |
1.0 |
0.9 |
1.8 |
13.5 |
290 |
1.83 |
2.33 |
82 |
78 |
67 |
1.43 |
1C X 16 |
0.7 |
1.0 |
0.9 |
1.8 |
14.0 |
350 |
1.15 |
1.47 |
108 |
101 |
92 |
2.29 |
1C X 25 |
0.9 |
1.0 |
1.6 |
1.8 |
16.0 |
470 |
0.727 |
0.927 |
139 |
134 |
123 |
3.58 |
1C X 35 |
0.9 |
1.0 |
0.9 |
1.8 |
17.0 |
570 |
0.524 |
0.668 |
165 |
154 |
146 |
5.00 |
1C X 50 |
1.0 |
1.0 |
1.25 |
1.8 |
19.0 |
750 |
0.387 |
0.494 |
199 |
199 |
180 |
7.15 |
1C X 70 |
1.1 |
1.0 |
1.25 |
1.8 |
21.0 |
980 |
0.268 |
0.342 |
244 |
239 |
230 |
10.01 |
1C X 95 |
1.1 |
1.0 |
1.25 |
1.8 |
22.5 |
1250 |
0.193 |
0.247 |
292 |
281 |
282 |
13.59 |
1C X 120 |
1.2 |
1.0 |
1.6 |
1.8 |
25.0 |
1550 |
0.153 |
0.197 |
332 |
315 |
328 |
17.16 |
1C X 150 |
1.4 |
1.0 |
1.6 |
1.8 |
26.5 |
1840 |
0.124 |
0.160 |
371 |
341 |
377 |
21.45 |
1C X 185 |
1.6 |
1.0 |
1.6 |
1.8 |
29.0 |
2210 |
0.0991 |
0.128 |
417 |
376 |
433 |
26.46 |
1C X 240 |
1.7 |
1.0 |
1.6 |
1.9 |
31.5 |
2820 |
0.0754 |
0.099 |
480 |
421 |
510 |
34.32 |
1C X 300 |
1.8 |
1.0 |
1.6 |
2.0 |
34.0 |
3390 |
0.0601 |
0.08 |
536 |
459 |
581 |
42.90 |
1C X 400 |
2.0 |
1.2 |
2.0 |
2.1 |
38.5 |
4370 |
0.0470 |
0.064 |
594 |
488 |
664 |
57.20 |
1C X 500 |
2.2 |
1.2 |
2.0 |
2.2 |
42.5 |
5440 |
0.0366 |
0.052 |
658 |
529 |
751 |
71.50 |
1C X 630 |
2.4 |
1.2 |
2.0 |
2.3 |
47.0 |
6900 |
0.0283 |
0.043 |
723 |
571 |
846 |
90.90 |
1C X 800 |
2.6 |
1.4 |
2.5 |
2.5 |
53.0 |
8880 |
0.0221 |
0.038 |
764 |
595 |
919 |
114.40 |
1C X 1000 |
2.8 |
1.4 |
2.5 |
2.7 |
58.0 |
10910 |
0.0176 |
0.033 |
810 |
632 |
997 |
143.0 |
|
Conductor up to 10 sqmm - stranded & circular |
Conductor of 16 sqmm - stranded & circular compacted |
Conductor above 16 sqmm - stranded & shaped |
(Note:- Solid & circular upto 10 sqmm & stranded & circular/circular compacted above 16 sqmm can be provided) |
|
CURRENT RATING GIVEN ABOVE BASED ON BELOW INSTALLATION CONDITIONS |
|
AMBIENT AIR TEMPERATURE- 50 DEGC |
GROUND TEMPERATURE- 35 DEGC |
DEPTH OF LAYING - 0.5 METERS |
SOIL THERMAL RESISTIVITY - 1.2 KM/WATT |
|
Notes: |
Unarmoured copper cables are also manufactured |
Cables as per various national / international standards such as IS/BS etc. / as per cutomer's requirement can also be manufactured |
These cables can also be supplied with Flame Retardant (FR) or Flame Retardant Low Smoke (FRLS) or Low Smoke Zero Halogen (LSZH) shealthing compounds as specific |
|
|