600/1000V XLPE INSULATED, PVC INNER SHEATHED,GALVANISED STEEL WIRE ARMOURED,PVC OUTER SHEATHED TWO CORE COPPER CABLES CONFIRMING TO IEC-60502-1 |
Type
|
No. of cores and cross sectional area
|
Thickness of XLPE insulation
|
Thicknewss of inner sheath
|
Single layer of round aluminium wire armour
|
Thickness of outer sheath
|
Overall diameter of cable
|
Net weight of cable
|
D.C. Resistance at 200C
|
A.C. Resistance at 900C
|
Current Rating
|
Short Circuit current rating for 1 sec
|
|
|
(nom.) |
(Approx.) |
(nom.) |
(nom.) |
(Approx.) |
(Approx.) |
(max.) |
(max.) |
Direct in ground |
In Duct |
In Air |
|
UNIT |
No. x mm2 |
mm |
mm |
mm |
mm |
mm |
Kg/km |
Ohm/km |
Ohm/km |
Amps |
Amps |
Amps |
KA(rms) |
2XWY |
2C X 1.5 |
0.7 |
1.0 |
0.9 |
1.8 |
14.0 |
360 |
12.1 |
15.43 |
33 |
27 |
24 |
0.21 |
2C X 2.5 |
0.7 |
1.0 |
0.9 |
1.8 |
15.0 |
410 |
7.41 |
9.45 |
42 |
35 |
32 |
0.36 |
2C X 4 |
0.7 |
1.0 |
0.9 |
1.8 |
16.0 |
480 |
4.61 |
5.88 |
56 |
46 |
43 |
0.57 |
2C X 6 |
0.7 |
1.0 |
0.9 |
1.8 |
17.0 |
550 |
3.08 |
3.93 |
70 |
58 |
55 |
0.86 |
2C X 10 |
0.7 |
1.0 |
1.25 |
1.8 |
19.5 |
810 |
1.83 |
2.33 |
94 |
77 |
74 |
1.43 |
2C X 16 |
0.7 |
1.0 |
1.25 |
1.8 |
21.0 |
960 |
1.15 |
1.47 |
121 |
99 |
98 |
2.29 |
2C X 25 |
0.9 |
1.0 |
1.6 |
1.8 |
22.0 |
1230 |
0.727 |
0.93 |
157 |
127 |
128 |
3.58 |
2C X 35 |
0.9 |
1.0 |
1.6 |
1.8 |
23.5 |
1470 |
0.524 |
0.67 |
188 |
153 |
158 |
5.00 |
2C X 50 |
1.0 |
1.0 |
1.6 |
1.9 |
26.0 |
1810 |
0.387 |
0.49 |
223 |
181 |
190 |
7.15 |
2C X 70 |
1.1 |
1.0 |
1.6 |
2.0 |
29.0 |
2350 |
0.268 |
0.34 |
273 |
224 |
239 |
10.01 |
2C X 95 |
1.1 |
1.2 |
2.0 |
2.1 |
33.5 |
3210 |
0.193 |
0.25 |
328 |
269 |
295 |
13.59 |
2C X 120 |
1.2 |
1.2 |
2.0 |
2.2 |
36.0 |
3810 |
0.153 |
0.197 |
372 |
307 |
341 |
17.16 |
2C X 150 |
1.4 |
1.2 |
2.0 |
2.3 |
39.5 |
4500 |
0.124 |
0.160 |
417 |
345 |
289 |
21.45 |
2C X 185 |
1.6 |
1.4 |
2.5 |
2.5 |
44.5 |
5800 |
0.0991 |
0.130 |
470 |
391 |
449 |
26.46 |
2C X 240 |
1.7 |
1.4 |
2.5 |
2.7 |
49.0 |
7180 |
0.0754 |
0.102 |
544 |
453 |
530 |
34.32 |
2C X 300 |
1.8 |
1.6 |
2.5 |
2.8 |
53.5 |
8530 |
0.0601 |
0.081 |
609 |
509 |
605 |
42.90 |
2C X 400 |
2.0 |
1.6 |
2.5 |
3.1 |
59.0 |
10530 |
0.0470 |
0.0606 |
687 |
575 |
696 |
57.2 |
|
Conductor up to 10 sqmm - stranded & circular |
Conductor of 16 sqmm - stranded & circular compacted |
Conductor above 16 sqmm - stranded & shaped |
(Note:- Solid & circular upto 10 sqmm & stranded & circular/circular compacted above 16 sqmm can be provided) |
|
CURRENT RATING GIVEN ABOVE BASED ON BELOW INSTALLATION CONDITIONS |
|
AMBIENT AIR TEMPERATURE- 50 DEGC |
GROUND TEMPERATURE- 35 DEGC |
DEPTH OF LAYING - 0.5 METERS |
SOIL THERMAL RESISTIVITY - 1.2 KM/WATT |
|
Notes: |
Unarmoured copper cables are also manufactured |
Cables as per various national / international standards such as IS/BS etc. / as per cutomer's requirement can also be manufactured |
These cables can also be supplied with Flame Retardant (FR) or Flame Retardant Low Smoke (FRLS) or Low Smoke Zero Halogen (LSZH) shealthing compounds as specific |
|
|