cords cable industries
600/1000V XLPE INSULATED, PVC INNER SHEATHED,GALVANISED STEEL WIRE ARMOURED,PVC OUTER SHEATHED FOUR CORE WITH REDUCED CORE COPPER CABLES CONFIRMING TO IEC-60502-1
Type No. of cores and cross sectional area Thickness of XLPE insulation Thicknewss of inner sheath Single layer of round aluminium wire armour Thickness of outer sheath Overall diameter of cable Net weight of cable D.C. Resistance at 200C A.C. Resistance at 900C Current Rating Short Circuit current rating for 1 sec
    Main conductor (nom.) Reduced conductor(nom.) (Approx.) (nom.) (nom.) (Approx.) (Approx.) (Main conductor)(max.) (Main conductor)(max.) Direct in ground In Duct In Air  
UNIT No. x mm2 mm mm mm mm mm mm Kg/km Ohm/km Ohm/km Amps Amps Amps KA(rms)
2XWY 3C X 25/16 0.9 0.7 1.0 1.6 1.8 25.5 1730 0.727 0.93 131 107 109 3.58
3C X 35/16 0.9 0.7 1.0 1.6 1.8 27.0 2050 0.524 0.67 157 128 134 5.00
3C X 50/25 1.0 0.9 1.0 1.6 1.9 30.5 2620 0.387 0.49 187 152 163 7.15
3C X 70/35 1.1 0.9 1.2 2.0 2.1 36.0 3750 0.268 0.34 229 187 205 10.01
3C X 95/50 1.1 1.0 1.2 2.0 2.2 39.5 4740 0.193 0.25 274 226 253 13.59
3C X 120/70 1.2 1.1 1.2 2.0 2.3 43.5 5800 0.153 0.197 312 258 293 17.16
3C X 150/70 1.4 1.1 1.4 2.5 2.5 48.5 7220 0.124 0.160 349 291 335 21.45
3C X 185/95 1.6 1.0 1.4 2.5 2.7 53.0 8720 0.0991 0.130 394 329 386 26.46
3C X 240/120 1.7 1.2 1.6 2.5 2.9 59.0 10980 0.0754 0.102 455 380 456 34.32
3C X 300/150 1.8 1.4 1.6 2.5 3.0 64.0 13080 0.0601 0.081 509 427 519 42.90
3C X 400/185 2.0 1.6 1.6 3.15 3.3 72.0 17000 0.0470 0.0606 574 490 597 57.20
 
Conductor up to 10 sqmm - stranded & circular
Conductor of 16 sqmm - stranded & circular compacted
Conductor above 16 sqmm - stranded & shaped
(Note:- Solid & circular upto 10 sqmm & stranded & circular/circular compacted above 16 sqmm can be provided)
 
CURRENT RATING GIVEN ABOVE BASED ON BELOW INSTALLATION CONDITIONS
 
AMBIENT AIR TEMPERATURE- 50 DEGC
GROUND TEMPERATURE- 35 DEGC
DEPTH OF LAYING - 0.5 METERS
SOIL THERMAL RESISTIVITY - 1.2 KM/WATT
 
Notes:
Unarmoured copper cables are also manufactured
Cables as per various national / international standards such as IS/BS etc. / as per cutomer's requirement can also be manufactured
These cables can also be supplied with Flame Retardant (FR) or Flame Retardant Low Smoke (FRLS) or Low Smoke Zero Halogen (LSZH) shealthing compounds as specific
 
 
N E W S


Fatal error: Uncaught Error: Call to undefined function mysql_select_db() in /home/l72218peb8ib/cordscable/cordscable/footer1.php:11 Stack trace: #0 /home/l72218peb8ib/cordscable/cordscable/Technical_Details_14.php(434): include() #1 {main} thrown in /home/l72218peb8ib/cordscable/cordscable/footer1.php on line 11