cords cables industries
300/500 Volts Grade PVC insulated and PVC sheathed Instrumentation cables
PVC insulated, unscreened / overall screened armoured / unarmoured instrumentation cables conforming to BS:5308-II/86
                 
0.5 Sq.mm Single/Multipair PVC insulated and PVC sheathed cables
No. of pair  1 2(quad formation) 5 10
Cable Type Unarmd. Armd. Unarmd. Armd. Unarmd. Armd. Unarmd. Armd.
Conductor formation  16/0.2 16/0.2 16/0.2 16/0.2 16/0.2 16/0.2 16/0.2 16/0.2
Insulation thickness (Nom.) (mm) 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6
Max. Core diameter (mm) 2.35 2.35 2.35 2.35 2.35 2.35 2.35 2.35
Thickness of sheath / bedding (Nominal) (mm) 0.8 0.8 0.8 0.8 1.1 1.1 1.2 1.2
Diameter over sheath / bedding (mm) 6.0 6.0 6.9 6.9 12.1 12.1 16.2 16.2
Size of armour wire (mm)   0.9   0.9   0.9   1.25
Diameter over armour (mm)   7.8   8.7   13.9   18.7
Thickness of outer sheath (Nominal)(mm)   1.3   1.3   1.5   1.6
Nominal overall diameter (For information only) (mm) 6.0 10.4 6.9 11.3 12.1 16.9 16.2 21.9
                 
0.75 Sq.mm Single/Multipair PVC insulated and PVC sheathed cables
No. of pair  1 2(quad formation) 5 10
Cable Type Unarmd. Armd. Unarmd. Armd. Unarmd. Armd. Unarmd. Armd.
Conductor formation  24/0.2 24/0.2 24/0.2 24/0.2 24/0.2 24/0.2 24/0.2 24/0.2
Insulation thickness (Nom.) (mm) 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6
Max. Core diameter (mm) 2.55 2.55 2.55 2.55 2.55 2.55 2.55 2.55
Thickness of sheath / bedding (Nominal) (mm) 0.8 0.8 0.8 0.8 1.2 1.2 1.3 1.3
Diameter over sheath / bedding (mm) 6.3 6.3 7.3 7.3 13.3 13.3 17.7 17.7
Size of armour wire (mm)   0.9   0.9   1.25   1.6
Diameter over armour (mm)   8.1   9.1   15.8   20.9
Thickness of outer sheath (Nominal)(mm)   1.3   1.4   1.5   1.7
Nominal overall diameter (For information only) (mm) 6.3 10.7 7.3 11.9 13.3 18.8 17.7 24.3
                 
1.5 Sq.mm Single/Multipair PVC insulated and PVC sheathed cables
No. of pair  1 2(quad formation) 5 10
Cable Type Unarmd. Armd. Unarmd. Armd. Unarmd. Armd. Unarmd. Armd.
Conductor formation  7/0.53 7/0.53 7/0.53 7/0.53 7/0.53 7/0.53 7/0.53 7/0.53
Insulation thickness (Nom.) (mm) 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6
Max. Core diameter (mm) 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
Thickness of sheath / bedding (Nominal) (mm) 0.8 0.8 0.9 0.9 1.2 1.2 1.3 1.3
Diameter over sheath / bedding (mm) 7.3 7.3 8.7 8.7 15.4 15.4 20.6 20.6
Size of armour wire (mm)   0.9   0.9   1.25   1.6
Diameter over armour (mm)   9.1   10.5   17.9   23.8
Thickness of outer sheath (Nominal)(mm)   1.4   1.4   1.6   1.8
Nominal overall diameter (For information only) (mm) 7.3 11.9 8.7 13.3 15.4 21.1 20.6 27.4
 

Cables with number of pairs upto 50 can be supplied.
To obtain the diameters of these cables with a collective screen, add 1.0 mm to the diameters given above.


Multicore unscreened / overall screened cables are also manufactured as per BS:5308-II/86 / customer's requirements.

We can also supply polyethylene insulated instrumentation cables as per BS:5308-I/86.

We can also supply PVC / PE insulated instrumentation cables as per customer's requirements or as per various National / International standards such as IEC, BS, VDE, IS, BHEL, NTPC etc..

Conductor material shall be annealed bare copper or annealed tinned copper as required.

Insulation / sheathing material used is PVC, HR-PVC and Polyethylene as per customer's requirement.

Shielding material shall be as per customer's requirement. Some types of shielding materials used are given below:-
a) Aluminium mylar tape screening alongwith drain wire of ATC.
b) Copper tape screening alongwith drain wire of ATC.
c) ABC / ATC wire braiding

Armouring material in case of armoured cables can be of Galvanised steel round wire / strip as per customer's requirements.

Cables can also be supplied with Flame retardant(FR) or Flame Retardant Low Smoke(FRLS) or Low Smoke Zero Halogen(LSZH) sheathing compounds as per specific requirements of customer.

Electrical and Physical parameters of cables are maintained as per applicable standard / customer's requirements / as agreed between customer and Cords.
 

N E W S


Fatal error: Uncaught Error: Call to undefined function mysql_select_db() in /home/l72218peb8ib/cordscable/cordscable/footer1.php:11 Stack trace: #0 /home/l72218peb8ib/cordscable/cordscable/Technical_Details_3.php(1128): include() #1 {main} thrown in /home/l72218peb8ib/cordscable/cordscable/footer1.php on line 11