Technical Data for 1100 V Grade XLPE insulated Armoured Control cable Type 2XWY and 2XFY conforming to IS:7098-I/88
Type No. of cores and cross sectional area Conductor (Cu) Min. No. of wires Thickness of PVC insulation (Nom.) Thickness of commom covering mimimum Extruded/Wrapped Armouring Thickness of PVC Outer Sheath (Minimum) Approx. O.D. Approx. net weight of cable Max. D.C. resistance at 200C Approx. A.C. resistance at operating temp. 700C Approx. resistance at 50 Hz Approx. Capacitance per phase Current Rating Short circuit rating for 1 sec.
Flat Wire Round wire Direct in Ground In Duct In Air
No. x mm2 No. mm mm Size mm Dia mm mm mm Kg/km Ohm/km Ohm/km Ohm/km microF/km Amps Amps Amps KA(rms)
2XWY 2 x 1.5 1 0.7 0.3   1.4 1.24 12.5 340 12.1 15.5 0.107 0.15 33 29 29 0.21
3 x 1.5 1 0.7 0.3   1.4 1.24 13.0 380 12.1 15.5 0.107 0.15 25 22 22 0.21
4 x 1.5 1 0.7 0.3   1.4 1.24 13.5 410 12.1 15.5 0.107 0.15 25 22 22 0.21
5 x 1.5 1 0.7 0.3   1.4 1.24 14.5 460 12.1 15.5 0.107 0.15 24 21 21 0.21
6 x 1.5 1 0.7 0.3   1.4 1.24 15.5 520 12.1 15.5 0.107 0.15 22 19 19 0.21
7 x 1.5 1 0.7 0.3   1.4 1.24 15.5 530 12.1 15.5 0.107 0.15 21 18 18 0.21
10 x 1.5 1 0.7 0.3   1.4 1.24 18.5 700 12.1 15.5 0.107 0.15 18 16 16 0.21
2XFY 12 x 1.5 1 0.7 0.3   1.4 1.24 19.0 740 12.1 15.5 0.107 0.15 17 15 15 0.21
14 x 1.5 1 0.7 0.3   1.4 1.40 20.0 810 12.1 15.5 0.107 0.15 16 14 14 0.21
16 x 1.5 1 0.7 0.3 4 x 0.8   1.40 19.5 760 12.1 15.5 0.107 0.15 16 14 14 0.21
19 x 1.5 1 0.7 0.3 4 x 0.8   1.40 20.5 850 12.1 15.5 0.107 0.15 15 13 13 0.21
24 x 1.5 1 0.7 0.3 4 x 0.8   1.40 23.0 1020 12.1 15.5 0.107 0.15 13 12 12 0.21
27 x 1.5 1 0.7 0.3 4 x 0.8   1.40 23.5 1070 12.1 15.5 0.107 0.15 13 11 11 0.21
30 x 1.5 1 0.7 0.3 4 x 0.8   1.40 24.5 1160 12.1 15.5 0.107 0.15 12 11 11 0.21
37 x 1.5 1 0.7 0.3 4 x 0.8   1.40 26.0 1330 12.1 15.5 0.107 0.15 11 10 10 0.21
44 x 1.5 1 0.7 0.3 4 x 0.8   1.40 29.0 1560 12.1 15.5 0.107 0.15 11 9 9 0.21
52 x 1.5 1 0.7 0.3 4 x 0.8   1.56 30.5 1740 12.1 15.5 0.107 0.15 10 9 9 0.21
61 x 1.5 1 0.7 0.4 4 x 0.8   1.56 32.0 1970 12.1 15.5 0.107 0.15 9 8 8 0.21
YWY 2 x 2.5 1 0.7 0.3   1.4 1.24 13.5 390 7.41 9.48 0.0985 0.18 39 32 32 0.36
3 x 2.5 1 0.7 0.3   1.4 1.24 14.0 440 7.41 9.48 0.0985 0.18 34 30 30 0.36
4 x 2.5 1 0.7 0.3   1.4 1.24 14.5 480 7.41 9.48 0.0985 0.18 34 30 30 0.36
5 x 2.5 1 0.7 0.3   1.4 1.24 15.5 540 7.41 9.48 0.0985 0.18 31 28 28 0.36
6 x 2.5 1 0.7 0.3   1.4 1.24 17.0 620 7.41 9.48 0.0985 0.18 29 26 26 0.36
7 x 2.5 1 0.7 0.3   1.4 1.24 19.0 640 7.41 9.48 0.0985 0.18 24 21 21 0.36
YFY 10 x 2.5 1 0.7 0.3 4 x 0.8   1.24 19.5 730 7.41 9.48 0.0985 0.18 24 21 21 0.36
12 x 2.5 1 0.7 0.3 4 x 0.8   1.40 20.5 790 7.41 9.48 0.0985 0.18 22 20 20 0.36
14 x 2.5 1 0.7 0.3 4 x 0.8   1.40 21.5 880 7.41 9.48 0.0985 0.18 21 19 19 0.36
16 x 2.5 1 0.7 0.3 4 x 0.8   1.40 22.5 970 7.41 9.48 0.0985 0.18 20 18 18 0.36
19 x 2.5 1 0.7 0.3 4 x 0.8   1.40 25.5 1060 7.41 9.48 0.0985 0.18 19 17 17 0.36
24 x 2.5 1 0.7 0.3 4 x 0.8   1.40 26.0 1330 7.41 9.48 0.0985 0.18 17 16 16 0.36
27 x 2.5 1 0.7 0.3 4 x 0.8   1.40 27.0 1400 7.41 9.48 0.0985 0.18 16 15 15 0.36
30 x 2.5 1 0.7 0.3 4 x 0.8   1.56 29.0 1520 7.41 9.48 0.0985 0.18 16 14 14 0.36
37 x 2.5 1 0.7 0.3 4 x 0.8   1.40 32.5 1780 7.41 9.48 0.0985 0.18 15 13 13 0.36
44 x 2.5 1 0.7 0.4 4 x 0.8   1.56 34.0 2080 7.41 9.48 0.0985 0.18 14 12 12 0.36
52 x 2.5 1 0.7 0.4 4 x 0.8   1.56 37.5 2370 7.41 9.48 0.0985 0.18 13 12 12 0.36
61 x 2.5 1 0.7 0.4 4 x 0.8   1.56 36.0 2690 7.41 9.48 0.0985 0.18 12 11 11 0.36
 
Unarmoured copper cables are also manufactured.
 
Cables as per various national / international standards such as IEC, BS etc. / as per customer's requirement can also be manufactured.
 
Copper cables upto 6 Sq.mm can be supplied with solid / stranded conductor. 10 sq.mm can be supplied with stranded circular conductors. 16 sq.mm and above can be supplied with stranded circular or stranded and shaped conductors as per customer's requirement.
 
These cables can also be supplied with Flame retardant(FR) or Flame retardant Low smoke(FRLS) or Low Smoke Zero Halogen(LSZH) sheathing compounds as per specific requirements of customer.
N E W S


Fatal error: Uncaught Error: Call to undefined function mysql_select_db() in /home/l72218peb8ib/cordscable/cordscable/footer1.php:11 Stack trace: #0 /home/l72218peb8ib/cordscable/cordscable/Technical_Details_8.php(891): include() #1 {main} thrown in /home/l72218peb8ib/cordscable/cordscable/footer1.php on line 11